  • crmd20 minutes ago
    &gt; Because the alarm wire carried current only during a fault, an open 25-inch strap produced the same electrical state at the receiving end as a healthy power plant.<p>I’m a building automation and controls tech in Manhattan, and for this exact reason digital feedback points and alarms are always normally-closed, and analog points are 4-20mA. This allows differentiation between nominal zero values and a fault in the loop.<p>Disasters like this are what our best practices are borne from.